Battery Protect 12V/24V-100A

RELAY-VTBP.png
RELAY-VTBP.png

Battery Protect 12V/24V-100A

90.00

Protect your batteries from accidental excessive discharge by installing a BP100 between your battery positive and DC distribution buss or fuse box.  For loads under 100A.

Quantity:
Add To Cart

Opperation:

The BP100 is a programmable MOSFET that can handle up to 100A of continuous load current and surges up 600A (65A and 220A models are also available).  When properly programmed, the BP100 acts as a switch that opens (turns off loads) when the battery bank voltage drops below a certain threshold.  When the battery gets recharged, above a certain threshold it reconnects. 

When a low voltage is detected, there will be a 90 second delay before the load is disconnected.  This prevents loads with a start up surge from accidentally triggering the device.  When a battery is recharged, there is a 30 second delay before the load is reconnected after the restart voltage threshold has been crossed.

The remote jumper can be configured as disconnect switch.

Installation:

Install the BP100 between the battery bank positive and the DC load buss or fuse box with the IN post on the battery side and the OUT post going to the loads.  Do not connect to the OUT post until the BP100 is programmed.  Connect the black wire from the GND pin to the battery negative post or chassis.  Install a fuse or breaker (with a rating under 100A) between the BP100 and the battery.

Programming:

1)  Supply 12V power to BP (+ to IN post, - to GND pin).  When voltage is detected the top and bottom bar of the numerical display will flash.
2)  Remove the remote port plug (2 pin green terminal block with jumper).
3)  Connect PROG pin to -, GND, or chassis using a wire scrap.
4)  The display will begin cycling through the numerical values corresponding to different connect/reconnect voltages shown in the instruction manual.
5)  Once you see the desired setting remove the scrap wire from the PROG pin.  (6 is a common choice with a disconnect at 11.5V and a reconnect at 12.8V.)
6)  When the program mode is selected the display will flash between the mode number and a letter representing the relay function.
7)  After the display goes blank connect the PROG pin to -, GND or chassis again.  The display will begin cycling through the alphabetical Relay function options.  Choose “b” for Relay protection mode.
8)  Once you see the desired setting remove the ground from the PROG pin. The device will display the current settings.
9)  Connect the DC Loads to the OUT post.  Your batteries are now protected.

You may also be interested in:

Battery Protect 12/24V-65A
55.00

Protect your batteries from accidental excessive discharge by installing a BP65 between your battery positive and DC distribution buss or fuse box.  For loads under 65A.

Quantity:
Add To Cart
Battery Protect 12/24V-220A
120.00

Protect your batteries from accidental excessive discharge by installing a BP220 between your battery positive and DC distribution buss or fuse box.  For loads under 220A.

Quantity:
Add To Cart
 

Visit the Victron webpage BPR000100400